- Stainless steel distributor - manifold Kit D1”x 3/4” and Eurocon outputs with fully equipped flowmeters
- they are made of high-quality stainless-steel type AISI 304
- adjustment on each circuit using flow meters
- possibility of mounting the thermoelectric actuator for the automation of the installation
- number of ways: 2 - 12
- equipped with fill/drain valves, automatic air vents and valve
Connecting the circuits to the distributor - manifold kit
- Install at 40 - 90 cm above the ground.
- Fit the isolation valves to the ends of the distributor - manifold kit bars
- Loosen the return valve cover to open all circuits to be used
- Remove the plastic cover of the flowmeters
- Fully open the flowmeter
- Loosen the connection between the pipes and the manifolds
- Secure the nut, the brass ring and end part of the eurocon connector
- Tighten the connection between the connector and the manifolds
Filling the manifolds with water
- Fill the distributor and the hydraulic system with water using the filling valve
- Fill the distributor and the hydraulic system with water using the filling valve
- Check the tightness of the circuits, close the isolation valves and increase the pressure to 6 bar and hold it for 24 hours using the test pump by means of the filling/drain valve.
- If the pressure remains the same after 24 hours, lower the pressure to 1-1,5 bar using the drain valve.
- Adjust the flow rate for each circuit according to the design flow rate, by checking the guide line of the flowmeter
- If the pressure drops, check all connections and all circuits.